Formula: Runtime (hours) = (Battery Capacity (Ah) × Voltage (V) × Efficiency) ÷ Load (W). This gives a first-pass estimate — real-world runtime is also affected by battery age, temperature and discharge-rate derating, so always apply a safety margin and confirm against the battery manufacturer's discharge curve.

Typical Standby Requirements by System

SystemTypical Standby Requirement
Fire alarm panel (NFPA 72)24 hours standby + 5 min alarm
Fire alarm panel (BS 5839)24 hours standby + 30 min alarm (or 72h + 30min for some systems)
PAVA system (EN 54-4)24 hours standby minimum
Data centre UPS (Tier 3+)Runtime to generator start, typically 10–15 min